§ 38-43. Size vents for flammable liquid tanks.  


Latest version.
  • Each flammable liquid tank shall be vented through piping adequate in size to prevent blow-back of vapor or liquid at the fill opening while the tank is being filled. Minimum size of vents shall be in accordance with the following table:

    Minimum Requirements for Vent Size

    Capacity of Tanks Gallons Diameter of Vent
    0 to 500 1¼ inches
    501 to 3,000 1½ inches
    3,001 to 10,000 2 inches
    10,001 to 25,000 2½ inches
    25,001 to 50,000 3 inches
    50,001 to 100,000 3½ inches
    100,001 to 150,000 4 inches
    150,001 to 400,000 5 inches
    400,001 to 1,000,000 6 inches

     

(Ord. No. 3707-03, § 6, 11-24-2003)