§ 38-43. Size vents for flammable liquid tanks.
Latest version.
Each flammable liquid tank shall be vented through piping adequate in size to prevent blow-back of vapor or liquid at the fill opening while the tank is being filled. Minimum size of vents shall be in accordance with the following table:
Minimum Requirements for Vent Size
Capacity of Tanks Gallons Diameter of Vent 0 to 500 1¼ inches 501 to 3,000 1½ inches 3,001 to 10,000 2 inches 10,001 to 25,000 2½ inches 25,001 to 50,000 3 inches 50,001 to 100,000 3½ inches 100,001 to 150,000 4 inches 150,001 to 400,000 5 inches 400,001 to 1,000,000 6 inches